Technical specification
Sensing input
Voltage:190 ~ 264 VAC, 1 phase 2 wire
Frequency:50/60Hz Single Phase
Output
Voltage:Max. 90 VDC at 207 VAC
Current:Continuous 4A, Intermittent 10 A for 10 sec
Resistance:15 ohms min
Regulation:+/- 1.0% (with 4% engine governing)
Thermal drift:0.04% per °C change in AVR ambient
Under frequency protection
Set point:95% Hz
Unit power dissipation:12 watts maximum
ANALOGUE INPUT
Maximum input:+/- 5V dc
Sensitivity:1v for 5% Generator Volts (adjustable)
Input resistance:1k ohm
QUADRATURE DROOP INPUT:Max. sensitivity
0.07 A for 5% droop 0PF:Max. input
0.33 A